Kod Grid Nasional Moris — Kod Distribision, Version Desam 2022
Lobzektif Kod Distribision se pou etablir bann reg, prosedir, kondision ek standar ki gouvern fonksionnman, antretien ek devlopman Sistem Distribision pou asir enn sistem distribision kouran ki efikas, kordine ek ekonomik. Li osi definir bann prosedir ek bann kondision ki aplikab pou Lisansie Distribision ek tou Itilizater Sistem Distribision.
Lisansie Distribision ek osi bann Itilizater existan ek potansiel ki konekte ou pe rod konekte ar Sistem Distribision bizin respekte bann seksion pertinan Kod Distribision, inklir bann Zenerater ek Klian Distribie. Bann itilizater ki konekte ar Sistem Distribision bizin respekte Kod Distribision. Frontier Interkoneksion ant bann Sistem Transmision ek Distribision pou kouma finn definir dan Seksion TC 1.1 dan Kod Transmision.
Sa Kod Distribision-la kontenir bann prosedir pou fourni enn servis distribision elektrisite adekwa, san danze ek efikas dan tou bann rezion Moris, an prenan kont enn gran varyete Kondision Normal ek Evantyalite. Kan bann sitiasion inprevi arive, Lisansie Distribision pou azir kouma enn operater rezonab ek pridan pou swiv enn ou plizier sa bann kondision zeneral-la:
Bann itilizater bizin donn korperasion ek lasistans rezonab ki Operater Sistem rezonabman demande pou swiv bann kondision zeneral sa Seksion DC-la 2.
Lisansie Distribision ansam avek Aste-la pou responsab pou planifie devlopman Sistem Distribision. Lotorite-la pou donn bann gid politik Ministeryel pou devlopman sistem. Aste-la pou devlop bann prosedir pou elaborasion enn Plan Resours Integre (IRP) a lonterm (orizon 10 an, ki met azour sak lane), kot pou inplik bann parti prenan kle dan enn prosesis kolaboratif. Lisansie Distribision ek Lisansie Transmision pou responsab pou inplimant ameliorasion ek agrandiman bann Sistem Transmision ek Distribision kouma finn definir dan IRP.
Bann kriter planifikasion Sistem Distribision pou baze lor bann Pratik Itilite Pridan ek bann standar internasional pertinan. Prensip prinsipal se responsabilite Lisansie Distribision pou “mintenir ninport ki instalasion, laparey ou lokal ki ena enn lien avek so lisans dan enn tel leta ki li kapav ofer enn servis elektrik ki an sekirite, adekwa ek efikas”.
Sistem Distribision bizin planifie pou enn demann avek enn Fakter Pouvwar ant 0.90 kapasitif e 0.90 indiktif dan bann kondision normal.
Lisansie Distribision, an kolaborasion avek Single Buyer ek System Operator, pou antreprann bann letid interkoneksion sak fwa ki neseser, an partikilie pou determinn bann kondision interkoneksion ninport ki Sistem Itilizater ou Lizinn Zenerasion. Bann letid-la inklir:
DC 3.4.1 Previzion Lenerzi ek Demann: Bann itilizater ki konekte kot MV bizin donn zot bann previzion Lenerzi ek Demann pou omwin sink an ki swiv (previzion par mwa pou premie lane, anyel pou bann lane swivan).
DC 3.4.2 Data Sistem Distribision: Lisansie Distribision pou met a dispozision Aste Sinik ek Operater Sistem tou bann done ki pertinan pou Sistem Distribision, an partikilie bann transformater, bann laliyn kouran ek bann Inite Zenerasion Distribie.
DC 3.4.3 Bann done sistem itilizater: Pou bann koneksion LV: pouvwar maximem neseser ek tip sarz. Pou bann koneksion MV: Bann kondision pouvwar Aktif/Reaktif, tip sarz, kouran armonik maximem, detay lor bann varyasion sarz siklik.
Seksion DC 4 dan Kod Distribision li aplikab a tou bann Zenerater Distribie ki deza existe ou ki kapav konekte ar Sistem Distribision LV ou MV. Lisansie Distribision responsab pou tou bann laspe ki ena enn lien avek bann interkoneksion bann Zenerater Distribie, inklir lesanz linformasion, prosesis koneksion, spesifikasion konsepsion teknik, bann kondision sekirite ek sirveyans konformite avek bann standar. Lisansie Distribision kapav refiz koneksion enn Inite Zenerasion Distribie si sa menas sekirite ou kalite fournisman.
Lisansie Distribision pou prodir enn dokiman (Kod Grid DG) pou sak kategori Zenerasion Distribie, ki pou kouver bann laspe prosedir (proses koneksion ziska Lakor Koneksion) ek bann laspe teknik (bann kondision sekirite, konsepsion, konstriksion, tes, met an servis ek bann laspe administratif). Kod Grid DG pou aprouve par Lotorite.
Bann laspe teknik Kod Grid DG bizin kontenir omwin:
Enn lizinn zenerasion avek enn kapasite anrezistre plis ki 4 MW me pa depas 10 MW konekte atraver enn laliyn dedie a 22 seksion kV dan Sistem Transmision bizin respekte bann kondision ki aplikab pou MSDG 3.
DC 4.4.1 Fazibilite: Fazibilite konekte enn Lizinn Zenerasion Distribie pou konfirme par enn Letid Linpak Interkoneksion Rezo, ki pou fer par Lisansie Distribision, ka par ka.
DC 4.4.2 Letid Koneksion: Pou CEB SOLAR PHOTOVOLTAIC SCHEME (HOUSEHOLDS), bann aplikasion finn aloue a feeder konserne. Pou MSDG 1/2/3, Lisansie Distribision ek Aste Tousel determinn bann modifikasion neseser dan rezo par fer bann letid apropriye.
DC 4.4.3 Alokasyon Kapasite: Alokasyon kapasite pou bann feeder pou bann zenerater distribie pou fer an-akor avek bann regleman ek prosedir ki finn aprouve par Lotorite.
Lentegrite Sistem Distribision ek sekirite ek kalite fournitir pou bann Itilizater existan pa pou tom anba nivo standar akoz fonksionnman paralel (senkronize) bann Zenerater Distribie. Fonksionnman paralel DGP li otorize zis si li otorize par Lisansie Distribision ek Operater Sistem an akor avek bann scheme ek bann polisi aplikab.
Bann Zenerater Distribie pou donn Lisansie Distribision ek Aste Sinik linformasion lor Lizinn Zenerasion ek bann laranzman interfas ki finn propoze. Bann linformasion neseser inklir an partikilie:
DC 4.7.1.1 Bann laranzman koneksion: CEB SOLAR PHOTOVOLTAIC SCHEME (HOSEHOLDS) konekte a 230/400 V; MSDG 1 konekte a 22 kV atraver enn transformater dedie; MSDG 2 ou MSDG 3 konekte atraver 22 Panel switchgear kV ek transformater step-up interkoneksion.
DC 4.7.1.2 Transformater Interkoneksion: MSDG 1/2/3 transformater interkoneksion bizin dan group vekter Dyn11 (Delta lor kote rezo, zetwal lor kote DGP). Bobin delta lor kote Sistem Distribision: (i) pa deranz proteksion kont defo later sou-stasion-la; (ii) anpes bann trip armonik ariv lor Rezo-la; (iii) izol DGP depi bann bes tansion akoz bann defo later monofaz. Bann group vekter alternativ kapav servi si laprouvasion Lisansie Distribision.
DC 4.7.1.3 Later:
DC 4.7.1.4 Emision Elektromayetik ek Iminite: Sistem zenerasion distribie bizin respekte bann kondision IEC 61000.
DC 4.7.1.5 Kapasite pou reziste bann vag: Instalasion interkoneksion bizin ena enn kapasite reziste bann vag (osilater ek tranzitwar rapid) an-akor avek IEC 62305-3 (bann nivo tes 1.5 kV). Konsepsion bann sistem kontrol bizin zwenn ouswa depas bann kondision IEEE C37.90.
Kordinasion ek selektivite sistem Proteksion bizin proteze. Sistem Proteksion pou protez kont bann defo ki arive lor Sistem Distribision ek bann instalasion elektrik DGP (kourt-sirkwi, defo later, sirsarz) ek anpes bann zil.
Zenerater Distribie bizin fer sir ki tou so bann instalasion elektrik proteze a tou moman. DGP bizin proteze kont: sirsarz, kourt-sirkwi, defo later, sirkouran, tansion abnormal, frekans abnormal, zekler ek pert kouran prinsipal (ROCOF ek shift vekter).
Bann Inite Zenerater Distribie pa pou fourni Sistem Distribision apre formasion enn Power Island. DGP pou dekonekte depi Sistem Distribision dan 0.5 segonn formasion enn Power Island (pert proteksion prinsipal, Tab 3).
Apre enn dekoneksion ki finn inisie par Proteksion, DGP pou res dekonekte depi Rezo-la ziska ki tansion ek frekans dan Frontier Interkoneksion finn res dan limit Kondision Normal pou omwin 3 minit. Rekoneksion otomatik li otorize zis kan dekoneksion-la ti akoz bann paramet fonksionnman andeor bann ranze normal.
Zenerater Distribie pou bizin fourni ek instal bann lekipman senkronizasion otomatik. Bizin met enn Rele Verifikasion Sinkronism lor tou bann disjonkter zenerater ek tou bann lezot disjonkter ki kapav konekte bann instalasion DGP ar Sistem Distribision.
Scheme inter-deklansman bizin desine ek pre-file dan enn fason ki deklansman disjonkter alimantasion interkoneksion a 22 Sistem Distribision kV Substation koz deklansman CB1. Sa scheme-la li konekte me inisyalman dezaktive pou bann Kapasite Anrezistre ziska 4 MW selman.
Bann Santral Soler PV: (1) Pandan lizour, kan 22 Disjonkter kV si ena defo, Inzenier Kontrol Sistem ouver CB1 a distans, ki inter-deklans CB2 ek tou lezot disjonkter sorti. Apre restorasyon provizion, CB1 finn re-ferme a distans e kontak sit MSDG finn re-ferme. (2) Aswar, disjonkter CB1 pa ouver parski pena zenerasion PV.
Fonksion "watchdog" rele proteksion-la pou bizin donn enn alarm dan ka enn defo. Pou bann DGP avek enn Kapasite Anrezistre plis ki 1,000 kW, sa signal alarm-la pou (si neseser) transmet a Substation Sistem Distribision atraver fib optik ou kominikasion san fil.
Pou bann DGP avek enn Kapasite Anrezistre plis ki 500 kW, Zenerater Distribie bizin soumet a Lisansie Distribision bann konfigirasion apropriye pou grad ek diskriminasion proteksion interkoneksion (22 disjonkter kV lor kote Sistem Distribision) avek proteksion anler. Zenerater Distribie bizin osi soumet kontribision kouran defo DGP (trwa-faz ek enn-faz-a-later).
Anplis bann sistem obligatwar interlocking (IEC 62271-200), enn mekanizm interlok apropriye pou anpes fermtir mekanik CB1 lor enn bar ki ena lenerzi lor kote klian. Pou bann masinn sinkron/asinkron: (a) enn relay verifikasion senkronism "Dead Bus Live Line" pou anpes fermtir elektrik/a distans CB1 si 22 kV busbar li alimante; (b) enn relay verifikasion senkronism lor tou bann disjonkter zenerater ki kapav konekte DGP ar Rezo-la.
Bann Zenerater Distribie bizin notifie Operater Sistem ek Lisansie Distribision si zot Lizinn Zenerasion ena enn Kapasite Black Start (kapasite pou relans Inite Zenerasion dan labsans alimantasion Rezo).
Bann instalasion elektrik DG pa bizin koz bann exkirsion tansion exsesif ni devier depi ranze ki Operater Sistem mintenir. Enn DGP pa bizin prodir enn distorsion exsesif lor tansion sinusoidal ouswa bann form vag kouran, e bizin an-akor avek DC 6.
Zenerater Distribie bizin fer bann tes ek pre-komisionnman an-akor avek bann standar pertinan e gard bann rezis ekri bann rezilta. Lisansie Distribision ena drwa pou demann bann tes ad hoc (nivo distorsion armonik, ogmantasion tansion, fonksionnman proteksion, lanket lor bann defo).
Tes ek pre-komisyonn CEB SOLAR PHOTOVOLTAIC SCHEME (HOUSEHOLDS) ek MSDG 1 instalasion pou fer par enn Instalater.
Pou bann proze Greenfield, Distributed Generator bizin soumet bann prosedir tes a Distribution Licensee pou laprouvasion omwin 3 mwa avan dat operasion komersial ki finn planifie. Bann tes pou fer par enn Inzenier Profesionel Anrezistre (MSDG 2) ou Inzenier Indepandan (MSDG 3).
Faz tes-la inklir omwin:
Zis pou bann santral PV soler: polarite lakord modil, Voc ek Isc, rezistans izolasion array PV. Pou bann santral eolienn: nivo vibrasion, vwayaz lor vites, bann tes kondwit yaw. Faz pre-komisionnman (dan prezans Lisansie Distribision ek Operater Sistem) inklir: bann tes mezir pouvwar aktif, bann tes fonksionel relay, 22 Enerzizasion kV, kapasite pouvwar reaktif, kalite pouvwar (IEC 61400-21), tes anti-lizil.
Zenerater Distribie bizin soumet enn Sertifika Instalasion signe par Installer / RPE / IE. Apre konformite, Lisansie Distribision pou emet enn Sertifika Konformite konfirme ki instalasion-la an-akor avek Kod Distribision e li adapte pou koneksion avek Sistem Distribision.
Operasion paralel avek Sistem Distribision pa otorize pou bann Zenerater Standby amwin ki Operater Sistem-la dakor. Bann klian ki ena bann Zenerater Standby bizin fer sir ki ninport ki parti instalasion ki zenerater-la fourni, dekonekte avan depi Sistem Distribision. Bizin met bann sign avertisman lor bann poto LV ek MV ek bann transformater kot ena enn Zenerater Standby konekte.
Dan ka non-konformite, Lisansie Distribision inform Zenerater Distribision par ekri lor bann dekalaz. Zenerater Distribie ena:
Apre sa peryod-la, Lisansie Distribision ena drwa dekonekte Zenerater Distribie. Rekoneksion bizin ki Lisansie Distribision sertifie ki instalasion-la an-akor avek Kod Distribision.
Enn UPS online neseser pou fer sir ki bann sistem proteksion, mezir, kontrol ek kominikasion fonksionn san interupsion pou omwin 3 ler apre pert provizion rezo. Dan ka pert provizion oksilier sekirize, tou 22 Bann disjonkter kV Zenerater Distribie bizin deklanse. Pou bann DGP avek enn Kapasite Anrezistre ≥ 1 MW, tou bann lekipman kominikasion bizin fourni par enn UPS separe.
Bann alarm ek bann vwayaz bizin ena indikasion lokal e, pou bann DGP avek enn Kapasite Anrezistre ≥ 1 MW, enn seri kontak san potansiel pou transmision anba ziska Substation Sistem Distribision. Bizin instal bann lalanp indikater extern pou bann DGP avek enn Kapasite Anrezistre > 200 kW: lalanp rouz = operasion paralel; lalanp ver = loperasion izole.
Bann DGP ki konekte ar rezo MV avek enn Kapasite Anrezistre plis ki 2 MW bizin soumet enn previzion Zenerasion Distribie a Lisansie Distribision ek Operater Sistem an-akor avek bann kondision SOC 4.2.4.
Enn DGP avek enn Kapasite Anrezistre > 1 MW pou soumet so plan antretien prevantif a Operater Sistem sak lane. Lisansie Distribision bizin kominik so bann plan antretien a bann DGP ki konekte ar rezo MV omwin enn semenn avan aksion ki finn planifie. Pena okenn konpansasion ki aplike pou okenn pert zenerasion akoz antretien prevantif ek korektif lor rezo Sistem Distribision.
DC 4.15.5.1 Fault Ride-Through (LVRT): DGP pou res konekte ar Sistem Distribision pou bann bes tansion faz kot tansion ki finn mezire dan Pwin Livrezon res lao kourb profil dire-tansion (Figure 1 pou bann masinn sinkron/asenkron, Fig 2 pou bann santral elektrik). Anplis, DGP bizin fourni Pouvwar Aktif an proporsion a voltaz ki finn retenir e maximiz kouran reaktif ki finn inzekte dan Sistem Distribision.
DC 4.15.5.2 Repons Frekans: Enn DGP avek enn Kapasite Anrezistre ≥ 1 MW pou bizin donn enn repons kouran-frekans an-akor avek Fig 3 (rediksion kouran lao 50.5 Hz a 40 %/Hz; rekoneksion zis kan frekans retourn a ≤ 50.5 Hz). Dekoneksion < 0.5 s si frekans > 52 Hz ou < 47 Hz.
DC 4.15.5.3 Kontrol pouvwar reaktif: Enn DGP avek enn Kapasite Anrezistre ≥ 1 MW bizin ekipe avek bann fonksion kontrol Pouvwar Reaktif ki exklir zot kamarad: (a) Kontrol Fakter Pouvwar; ou (b) Kontrol pouvwar reaktif. Enn mod kontrol voltaz kapav osi neseser lor enn baz ka par ka.
DC 4.15.5.4 Limit To Ramp: Enn DGP avek enn Kapasite Anrezistre ≥ 1 MW pou ena enn to ranp maximem (anler ek anba) egal a Kapasite Anrezistre (MW) divize par 5 pou bann ranp 1-minit. Bann konfigirasion to ranp bizin aprouve par Operater Sistem avan met an servis. Pou ninport ki sanzman ki pou swiv, bizin enn notis minimem de semenn.
Enn DGP bizin instale an-akor avek bann instriksion fabrikan. Instalater-la bizin pran kont: demann maximem, tip sistem later, natir ofrand, linflians extern, konpatibilite/antretien/aksesibilite, proteksion kont sok elektrik ek bann lefe termik, proteksion kont sirkouran, izolasion ek switching. Instalater-la bizin afis enn etiket ki indik klerman prosin antretien ki li finn planifie. Instalater-la bizin kalifie dan domenn bann instalasion elektrik DGP e bizin ena enn sertifika aprouve.
Enn MSDG 2 avek enn Kapasite Anrezistre ≥ 1 MW ou MSDG 3 pou instal bann lekipman kominikasion pou transfer an sekirite bann done operasionel ek bann signal proteksion ek kontrol atraver: (a) bann kab fib optik (DGP avek Kapasite Anrezistre ≥ 1 MW); (b) 4G/LTE (via VPN) ou Microwave link kouma enn kanal kominikasion backup. Zenerater Distribie-la sarye kou pou instal kominikasion depi DGP ziska Substasion korespondan.
Bann done ki pou transmet inklir:
Bann kominikasion san fil (si servi) bizin servi 3G/4G/LTE ou enn teknolozi pli resan, enn lien Microwave kouma kanal primer ek 3G/4G/LTE kouma backup, kapasite dual-SIM, bann tinel VPN, de router dan konfigirasion primer/hot-standby, to data ≥ 85 kbps anba / 42 kbps anler.
Sa seksion-la spesifie metod normal pou interkoneksion avek Sistem Distribision ek bann kriter teknik, konsepsion ek operasionel minimum avek ki sak Itilizater bizin respekte. Tou bann kou ek responsabilite interkoneksion normalman responsab par Itilizater ki konekte ar Sistem Distribision.
DC 5.4.1 Bann interkoneksion ba voltaz: Fournitir finn fourni kouma enn sel faz 230 V ou trwa-faz 400 V. Bann linformasion neseser pou bann interkoneksion LV inklir omwin: Nom/ladres klian, lokalizasion, tip interkoneksion, kapasite neseser, idantifikasyon bann gran moter ouswa lekipman soudman.
DC 5.4.2 Interkoneksion mwayen tansion: Avan premie energizasion enn Sistem Itilizater, bizin fourni sa bann done-la a Lisansie Distribision: bann done azour, bann diagram proteksion, Diagram Operasion, lalis bann Kordinater Sekirite, bann Plan Sit Komin.
Bann Interkoneksion Zenerater bizin respekte bann kondision pertinan Kod Zenerasion ek Seksion DC 4. Operater enn Lizinn Zenerasion Distribie pou opere ek mintenir bann Inite Zenerasion dan enn fason ki pa afekte dan enn fason negatif Sistem Distribision ek lezot Itilizater.
Tou bann Itilizater ki konekte ar Sistem Distribision bizin mintenir kalite form vag tansion dan Frontier Interkoneksion dan bann limit ki finn spesifie dan sa seksion-la.
DC 6.2.1 Voltaz: Lisansie Distribision bizin limit bann armonik tansion laliyn-a-net anba bann valer rekomande dan IEEE 519 pou bann frontier interkoneksion tou bann itilizater (Tab 4).
DC 6.2.2 Kouran:
DC 6.3.1 Voltage Flicker: An-akor avek bann valer maximem dan Frontier Interkoneksion ki finn spesifie dan IEC TR 61000-3-7 (MV) ek IEC TR 61000-3 parti 3 ek 11 (LV).
DC 6.3.2 Bann varyasion voltaz:
95em poursantaz dezekilib faz (voltaz) par semenn, kalkile an-akor avek IEC 61000-4-30 ek IEC 61000-3-13, pou ≤ 1.3 % lor Sistem Distribision, exsepte dan bann kondision abnormal.
DC 6.5.1 Limitasion inzeksion DC: Enn Klian ou enn Zenerater Distribie pa bizin inzekte enn kouran direk plis ki 0.25 % kouran sorti AC nominal par faz. Enn Zenerater/Klian ki konekte ar rezo LV pa bizin inzekte enn kouran DC pli gran ki pli gran valer ant 20 mA ek 0.25 % kouran sorti AC nominal par faz.
DC 6.5.2 Dezekilib Voltaz ek Kouran: Dezekilib voltaz total dan Rezo-la bizin mwins ki 2 %. Kontribision a nivo dezekilib tansion dan Frontier Interkoneksion enn Lizinn Zenerasion Distribie pou ≤ 1.3 %.
Tou bann instalasion elektrik ki ena enn lien avek bann Itilizater/Lisansie dan Frontier Interkoneksion bizin respekte bann kondision DC 7 ek so bann sou-seksion.
Tou bann disjonkter, dekonekter, laparey met later, transformater kouran, transformater tansion, transformater kouran, arestater ek lezot lekipman lor Sit Interkoneksion bizin konstrir, instale ek teste an akor avek bann standar teknik ki finn spesifie par Lisansie Distribision ek bann Pratik Itilite Pridan. Bann instalasion ek bann switchgear bizin desine, fabrike ek teste dan ISO 9001-bann lokal sertifie ou ekivalan.
Tou bann sistem ek konfigirasion proteksion bizin an-akor avek Polisi Proteksion Lisansie Distribision. Proteksion Sistem Distribision ek bann Klian bizin desine, kordine ek teste pou izol bann parti afekte dan Sistem-la a vites ek sansibilite neseser, anmemtan ki mintenir bann provizion pou leres Sistem-la. Lisansie Distribision tousel responsab pou proteksion Sistem Distribision; Zis bann itilizater ki responsab pou proteksion zot bann sistem lor zot kote Frontier Interkoneksion.
Responsabilite pou konstriksion, met an servis, kontrol, fonksionnman ek antretien bann Instalasion Elektrik determine dapre propriete sak instalasion, amwin ki enn lakor ant bann Parti prevwar otreman.
Lisansie Distribision ek tou Itilizater Sistem Distribision bizin respekte bann regleman elektrik pertinan. Avan interkoneksion MV, Lisansie Distribision ek Itilizater bizin konklir enn lakor an ekri lor bann Regleman Sekirite ki pou servi pou bann travay dan bann Instalasion dan Frontier Interkoneksion (SOC 15).
Enn Tablo Responsabilite Sit pou prodir pou Operater Sistem ek bann Itilizater avek ki li interfas (format dapre DC 21.1). Sa bann dokiman-la pou inklir dan IA, ESPA, CA ou PPA.
DC 8.4.1 Plan proze: Itilizater pou prepar ek soumet 3 kopi tou bann desin a Lisansie Distribision ek Operater Sistem pou revizion (revizion dan 15 zour). Dan 90 zour depi Dat Operasion Komersial, Itilizater-la pou bizin fourni enn seri konple bann desin kouma finn konstrir (2 kopi lor papie ek version elektronik PDF).
DC 8.4.2 Diagram fonksionnman: Enn Diagram Fonksionnman pou bizin prepare par Itilizater pou sak Sit Interkoneksion an-akor avek DC 21.2.
DC 8.4.3 Plan Sit Komin: Itilizater prepar ek soumet bann Plan Sit Komen pou so kote Frontier Interkoneksion. Lerla Lisansie Distribision prodir ek distribie bann Plan Sit Komen konple pou Sit Interkoneksion an antie.
Bann laranzman pou akse a bann sit Lisansie Distribision par bann Itilizater, ek vis versa, pou definir dan sak IA, ESPA, CA ou PPA. Demann-la bizin detaye ek soumet 3 zour travay alavans.
Pou bann rezon sa seksion-la, term Itilizater fer referans a bann Zenerater Distribie ek bann Klian ki konekte ar Sistem Distribision MV. Telekominikasyon ant Itilizater (bann) ek Operater Sistem bizin etablir si Operater Sistem bizin. Telefoni kontrol se mwayin par ki bann Inzenier Operasion kominike pou kontrol Sistem Distribision, dan bann sitiasion normal ek irzan. Itilizater-la bizin instal bann lekipman telefonik apropriye si so instalasion pa konpatib avek sistem Operater-la.
Operater Sistem-la pou bizin fourni enn interfas outstation SCADA. Itilizater-la pou bizin fourni 4–20 mA bann signal mezir pou voltaz, kouran, frekans, Pouvwar Aktif ek Pouvwar Reaktif, ek osi bann pozision lekipman ek bann alarm pou lekipman SCADA ki ena dan stasion operater sistem (an-akor avek DC 21.3).
Pou ki Sistem Distribision fonksionn dan enn fason efikas ek an-akor avek bann kondision Lisans, Lisansie Distribision avek soutien Operater Sistem pou organiz ek fer bann tes ek/ou sirveyans lefe bann Instalasion Itilizater lor Sistem Distribision.
Lobzektif DC 10 se pou spesifie kondision pou bann tes ek/ou sirveyans pou fer sir ki bann Itilizater pa pe fonksionn andeor bann paramet teknik ki Kod Distribision demande.
Operater Sistem periodikman determinn nesesite pou teste ek/ou sirvey kalite kouran. Sa bann tes-la fer lor depans Operater Sistem. Si enn kont-tes demande par Itilizater, li fer a depans Itilizater. Enn Itilizater ki pe fonksionn andeor bann limit bizin rektifie sitiasion-la ouswa dekonekte Lekipman ki pe koz problem-la toutswit ouswa dan enn dele letan ki finn tom dakor avek Operater Sistem-la.
Operater Sistem periodikman sirvey bann kouran pouvwar Aktif ek Reaktif dan Frontier Interkoneksion. Tou bann kou ki ena enn lien avek ogmantasion kapasite fizik Frontier-la, se Itilizater-la ki pe sarye.
Operater Sistem etablir bann kondision pou bann Itilizater ek Klian Sistem Distribision pou permet rediksion dan demann total dan ka enn zenerasion insifis pou reponn a demann total, ouswa pou evit dekonekte bann Klian ek Itilizater, ouswa dan ka enn defayans ek/ou enn sirsarz lor ninport ki parti bann Sistem Transmision ek/ou Distribision. Bann prosedir Kontrol Demann viz pou minimiz difikilte pou bann Itilizater e pou tret tou bann parti afekte dan enn fason ekitab. Operater Sistem ek Itilizater bizin respekte bann kondision ki finn etablir dan seksion SOC 9 dan Kod Operasion Sistem.
Operater Sistem ek Itilizater pou esanz linformasion pou ki kapav konsider bann inplikasion enn Operasion ek/ou enn Insidan, evalye bann risk potansiel ek pran bann aksion apropriye pou mintenir lentegrite Sistem Total ek bann Instalasion Itilizater. Operater Sistem ek Itilizater bizin respekte bann kondision ki finn etablir dan seksion SOC 11 dan Kod Operasion Sistem.
Tou bann Instalasion ek Lekipman Sistem bizin fonksione ek mintenir an-akor avek bann Pratik Itilite Pridan e dan enn fason ki pa konstitie enn menas pou sekirite bann anplwaye ou piblik. Operater Sistem-la pou etablir enn Polisi Mintenans Sistem Distribision ki pou revize ek aprouve par Lotorite. Lisansie Distribision pou kordinn avek Operater Sistem pou antretien planifie bann instalasion MV dan Sistem Distribision. Operater Sistem, Lisansie Distribision ek ninport ki Itilizater konekte bizin respekte bann kondision etablir dan seksion SOC 12 dan Kod Operasion Sistem.
Switching Voltaz Mwayenn pou fer zis avek permision Inzenier Kontrol Sistem ou zot bann reprezantan dezigne, exsepte dan ka enn Irzans Sistem. Bann dimounn ki bizin fer switching Medium Voltage bizin spesifikman sertifie ek otorize par Operater Sistem pou fer sa switching-la. Operater Sistem-la bizin respekte bann kondision ek prosedir seksion SOC 7 dan Kod Operasion Sistem.
Sa seksion-la definir bann responsabilite ek bann prosedir pou notifie bann proprieter konserne lor nimerotasion ek nomenklatir bann Lekipman dan bann Frontier Interkoneksion.
Lobzektif prinsipal se pou fer sir ki dan ninport ki Sit kot ena enn limit propriete, sak item Lekipman ena enn nimerotasion ek/ou nomenklatir ki finn tom dakor, pou asir Fonksionnman an sekirite ek efikas bann Sistem ki inplike e pou diminie risk erer.
Nouvo lekipman: Nimerotasion/nomenklatir ki finn propoze bizin notifie par ekri omwin 3 mwa avan instalasion ki finn prevwar. Resipian-la bizin reponn an ekri dan lespas enn mwa apre ki li finn resevwar.
Bann lekipman ki deza existe: Operater Sistem ek sak Itilizater responsab pou provizion ek plasman bann etiket kler ki indik nimerotasion ek nomenklatir zot Lekipman dan bann sit ki ena enn Frontier Interkoneksion.
Bann modifikasion: Kan bizin sanz nimerotasion/nomenklatir, bann mem prosedir aplike. Parti ki finn fer sanzman-la responsab pou met bann etiket-la azour.
Sa seksion-la definir bann responsabilite ek prosedir pou organiz ek fer bann Tes Sistem Spesial ki ena ouswa kapav ena enn lefe lor Sistem Distribision ouswa Sistem Itilizater. Bann Tes Spesial se bann ki inplik aplikasion simuler ou kontrole bann kondision iregilye, insolit ou extrem lor Sistem-la, exklir bann tes met an servis ou re-met an servis.
Bann lobzektif se: (a) pou fer sir ki bann prosedir pou organiz bann Tes Spesial pa menas sekirite personel ou piblik an zeneral e koz enn menas minimem pou sekirite bann fournitir ek lentegrite bann Instalasion; ek (b) pou definir bann prosedir ki bizin swiv pou etablir ek rapor bann Tes Sistem Spesial.
Kan enn Itilizater pe pans pou fer enn Tes Sistem Spesial, bizin donn enn notis 1 mwa davans a Lisansie Distribision ek bann Itilizater afekte. Operater Sistem ena kordinasion zeneral e li konvok enn Komite Tes. Sa dernie-la prodir enn rapor propozision dan lespas 2 mwa depi so premie renion. Si rapor-la finn aprouve dan enn fason inanim par tou bann benefisier, enn program tes final pou soumet omwin 1 mwa avan dat ki finn planifie. Enn rapor final prodir a lafin Tes-la e Komite-la dizourd.
Sa seksion-la definir manier ki bann kouran pouvwar ek lenerzi bizin mezire dan enn Interfas operasionel. Lisansie Distribision responsab pou akizision, instalasion, antretien, kalibrasion ek teste bann konter ek bann sistem konter, ek osi lektir konter, facture ek zestyon bann konplint Klian.
Presizion zeneral neseser (bann valer maximem ki permet):
Bann paramet ki bizin mezire inklir: Lenerzi Aktif (Wh) inportasion/exportasion, Lenerzi Reaktif (VARh) 1er ek 4em kadran, Demann Pouvwar Aktif ek Reaktif ek THD. Interval demann se 30 minit. Bann transformater mezir bizin an-akor avek IEC 61869.
Presizion zeneral neseser pou bann sistem mezir facture: ± 1 % dan laboratwar ek ± 2 % dan karo. Pou bann konter CT: ± 1.5 % (LV) ek ± 1 % (MV). Tou bann konter bizin an-akor avek bann dernie revizion IEC 62053 ou bann standar internasional ekivalan.
Pou bann konter CT, Pwin Livrezon trouv dan pozision bann Transformater Kouran ki servi pou sistem konter, ki finn desine pli pre posib ar Frontier Interkoneksion. Bann transformater kouran bizin instale dan enn konpartiman separe, anler a switch prinsipal.
Tou bann konter bizin kalibre dan lizinn. Kalibrasion bann konter elektronik fer zis dan lizinn. Ninport ki kalibrasion laboratwar bizin fer dan bann laboratwar akredite par Servis Akreditasion Moris (MAURITAS). Tou bann konter bizin ferme pou anpes akse non-otorize, avek enn indikasion dat re-kalibrasion ek nimero seri. Standar kilowatt-er ki servi pou kalibrasion bizin trasab a enn standar nasional ou internasional ki rekonet. Zis bann konter ki finn gagn laprouvasion tip depi Mauritius Standards Bureau (MSB) kapav servi.
Si Sistem Kontaz-la prouve ki li pa exakt par plis ki erer ki finn permet e ki Aste-la ek Zenerater/Itilizater Distribie pa pe kapav tom dakor dan enn dele letan rezonab, zafer-la kapav soumet a arbitraz. Enn Itilizater/Zenerater Distribie ena drwa demann enn verifikasion presizion konter. Si plis ki enn verifikasion demande dan mem lane kalandriye, Aste-la kapav sarz pou bann verifikasion adisyonel si presizion li dan ± 2 %.
An zeneral, sistem elektrik lil periferik Rodrig (enn ti sistem izole ki konpri de-trwa zenerater ek 22 kV feeders) bizin respekte bann kondision Kod Distribision, avek bann exsepsion swivan.
Operater Sistem-la pou servi Automatic Load Shedding par bann Rele Sou-Frekans pou zer bann dezekilib a kour term ant Pouvwar Total Sistem ek Demann. Demann ki size a dekoneksion otomatik bizin divize an bann blok MW separe. Apre 2 bann aktivasion, bann manzer a bann nivo 1 ek 2 pou kot posib esanz avek bann ki dan bann nivo pli ba pou pa penaliz bann mem Klian.
Sak Inite Zenerater ou Santral Elektrik dan Rodrig bizin ekipe avek enn laparey kontrol frekans ki azir rapid (Sistem Kontrol Gouverner) avek:
Lobzektif DC 19 se pou: (a) liste tou bann done ki pou fourni par bann Itilizater a Operater Sistem ek a Aste-r Sel; (b) liste tou bann done ki pou fourni par Operater Sistem a bann Itilizater; ek (c) liste tou bann done ki pou esanz avek bann Zenerater Distribie anba Kod Distribision.
Sak item done finn klase an trwa kategori:
Sak Itilizater pou bizin soumet bann done ki finn rezime dan DC 20 a Lisansie Distribision, ki apre partaz li avek Sel Aste ek Operater Sistem. Bann done kapav soumet par enn lien ordinater, lakle USB, CD ROM ou teknolozi cloud, apre enn konsantman ekri avan. Itilizater-la pou notifie Lisansie Distribision lor ninport ki sanzman dan bann done ki finn deza soumet. Si enn Itilizater pa fourni bann done neseser, Lisansie Distribision kapav estim li an kolaborasion avek Operater Sistem ek/ou Aste Tousel.
Bann linformasion swivan bizin depi sak Itilizater ki konekte ar Sistem Distribision atraver enn Frontier Interkoneksion:
Bann linformasion swivan bizin depi sak Itilizater ki konekte atraver enn Frontier Interkoneksion kot Sistem Itilizater-la kontenir enn ou plizier Inite Zenerater Distribie ek/ou bann sarz moter:
Sak Tablo Responsabilite Sit bizin: indik klerman propriete ek responsabilite sak item Lekipman dan Sit Interkoneksion; bizin signe lor nom Operater Sistem ek Itilizater avek dat; inklir dan IA, ESPA, CA ou PPA. Form standar-la inklir bann domenn: Lakonpani, Sit Interkoneksion, sinyatir ek dat toulede parti.
Kot posib, tou bann Lekipman MV dan ninport ki Sit Interkoneksion bizin reprezante lor enn sel Diagram Fonksionnman. Laranzman-la bizin reprezant avek otan presizion ki posib laranzman zeografik dan Sit Interkoneksion. Bann diagram fonksionnman bizin montre avek presizion stati aktyel bann lekipman (an servis/andeor servis). Bann item ki pou reprezante inklir an partikilie: bann bar bis, bann disjonkter, bann dekonekter ek bann switch, bann laparey pou met later, bann transformater kouran, bann transformater mezir (kouran ek tansion), bann arete surge, bann zenerater black start. Tou bann sinbol grafik ki servi bizin aprouve par Operater Sistem.
Bann kondision zeneral pou bann signal SCADA bizin an-akor avek IEC 60870-2-1 ek IEC 60870-3 (konpatibilite elektromayetik). An partikilie:
DC 21.4.1 MSDG tipik 1 Laranzman Interkoneksion: Interkoneksion tipik pou MSDG 1 finn dekrir dan sa anex-la.
DC 21.4.2 Panel tipik MV Switchgear ek Gid Proteksion pou MSDG 2 ek MSDG 3: Bann not inportan inklir: